Wire Size Calculator

A
m
V
%
Recommended AWG
AWG 4
Cross-section
21.2 mm²
Voltage drop
0.326 V (2.72%)

How to Use the Wire Size Calculator

Wire gauge selection balances safety, voltage drop, and cost. Undersized conductors overheat under sustained current; oversized wire wastes copper and complicates terminations. National electrical codes set minimum ampacity for branch circuits, but long runs — solar arrays, shed subpanels, EV charger feeders — also require voltage-drop checks so equipment at the far end receives adequate voltage.

Voltage drop on a round-trip (out-and-back) DC or single-phase AC run is:

Vdrop = I × 2 × L × Rwire

Where I is load current in amperes, L is one-way length in meters, and Rwire is resistance per meter for the chosen AWG size. Select the smallest gauge whose drop stays below your limit — commonly 3% for branch circuits or 2% for sensitive loads.

AWG numbers run inverse to diameter: lower gauge means thicker wire and lower resistance. AWG 10 copper handles roughly 30 A in conduit; AWG 14 suits 15 A lighting circuits. Ampacity tables assume specific insulation temperature ratings and bundling — always verify against local NEC, IEC, or BS 7671 requirements for your installation type.

Worked example: A 12 V solar pump draws 8 A, 25 m one-way (50 m round trip). Allow 3% drop: max Vdrop = 0.36 V. AWG 14 (2.08 mm²) has ~0.0083 Ω/m → drop = 8 × 50 × 0.0083 = 3.32 V — too much. AWG 10 (5.26 mm²) at ~0.0033 Ω/m → drop = 1.32 V (11%) — still high. AWG 6 (13.3 mm²) at ~0.0013 Ω/m → drop = 0.52 V (4.3%). AWG 4 (21.2 mm²) → drop ≈ 0.33 V (2.7%) — acceptable. The calculator automates this search across standard AWG sizes.

Pair with the AWG-to-mm² converter for metric projects and the PCB trace width calculator for board-level current paths.

AWG wire sizes (copper)

AWGmm²Ø (mm)Max A (approx)
142.081.634.5
123.312.057
105.262.5911
88.373.2618
613.34.1128
421.25.1945
233.66.5472

Frequently asked questions

3% on branch circuits is a common NEC guideline; 2% or less for critical or low-voltage runs where small absolute drops matter more.

No. This tool focuses on voltage drop. Always verify ampacity, insulation type, ambient temperature, and conduit fill per your local code.

Current travels out on the hot conductor and returns on neutral or ground, so resistance applies to the full round-trip path.

Related tools

Related conversions